5 Control inputs and outputs
5.1 Analog input EM-S1INA
5.1.1 General
The analog input of the EM-RES-01 expansion module can optionally be configured as
a voltage or a current input. Parameterization of the input signal is done by the defini-
tion of a linear characteristic and assignment as a
reference value source
(can be selected via the parameter
Reference frequency source 475),
reference percentage source
(can be selected via the parameter
Reference percentage source 476),
actual percentage source
(can be selected via the parameter
Actual percentage source 478, in configura-
tion x11) or
limit value sources
(can be selected via the parameters 734…737).
5.1.2 Configuration voltage/current input
The analog input of the EM-RES-01 expansion module has been confi
g
ured in the
factory setting for a voltage signal of +/- 10 V. Switch S3 enables a switch-over of the
operation mode for an analog current signal of +/-20 mA.
X410A
X
410B
S3
Operation mode – switch S3 Function
OFF -Voltage input
OFF (downward) –
analog input EM-S1INA is configured for a
voltage signal.
ON -Current input
ON (upward) –
analog input EM-S1INA is configured for a
current signal.