Operating instructions
08/06 49
5 Control inputs and outputs
5.1 Analog input EM-S1INA
5.1.1 General
The analog input of the EM-RES-01 expansion module can optionally be configured as
a voltage or a current input. Parameterization of the input signal is done by the defini-
tion of a linear characteristic and assignment as a
− reference value source
(can be selected via the parameter
Reference frequency source 475),
− reference percentage source
(can be selected via the parameter
Reference percentage source 476),
− actual percentage source
(can be selected via the parameter
Actual percentage source 478, in configura-
tion x11) or
− limit value sources
(can be selected via the parameters 734…737).
5.1.2 Configuration voltage/current input
The analog input of the EM-RES-01 expansion module has been confi
g
ured in the
factory setting for a voltage signal of +/- 10 V. Switch S3 enables a switch-over of the
operation mode for an analog current signal of +/-20 mA.
X410A
X
410B
S3
Operation mode – switch S3 Function
OFF -Voltage input
OFF (downward) –
analog input EM-S1INA is configured for a
voltage signal.
ON -Current input
ON (upward) –
analog input EM-S1INA is configured for a
current signal.