Operating instructions

08/06 13
4.4 Baud rate setting/line length
The setting of the baud rate must be identical in all subscribers on the system bus.
T
he maximum possible baud rate is based on the necessary overall line len
g
th of the
system bus. The baud rate is set via the parameter
Baud-Rate 903 and thus defines
the possible line length.
Operation mode Function max. line length
3 - 50 kBaud Transmission rate 50 kBaud 1000 meters
4 - 100 kBaud Transmission rate 100 kBaud 800 meters
5 - 125 kBaud Transmission rate 125 kBaud 500 meters
6 - 250 kBaud Transmission rate 250 kBaud 250 meters
7 - 500 kBaud Transmission rate 500 kBaud 100 meters
8 - 1000 kBaud Transmission rate 1000 kBaud 25 meters
A baud rate under 50 kBaud, as defined accordin
g
to CANopen, is not sensible for the
system bus as the data throughput is too low.
The maximum line lengths stated are guidelines. If they are made complete use of,
the admissible len
g
th is to be calculated on the basis of the line parameters and the
bus driver (PCA82C250T)
4.5 Setting node address
A maximum of 63 slaves or frequency inverters with system bus can be operated on
the system bus. Each frequency inverter is
g
iven a node ID, which may only exist
once in the system, for its unambi
g
uous identification. The settin
g
of the system bus
node ID is done via the parameter
Node-ID 900.
Parameter Setting
No. Description Min. Max. Factory setting
900 Node-ID -1 63 -1
T
hus, the system bus possesses a maximum number of 63 subscribers (Networ
k
nodes), plus one frequency inverter as a master.
Note:
With the factory setting of parameter
Node-ID 900 = -1, the system bus
is deactivated for this frequency inverter.
If the
Node-ID 900 = 0 is set, the frequency inverter is defined as a mas-
ter. Only one frequency inverter on the system bus may be defined as a
master.