Operating instructions

4911/06
11/06 49
5 Parameter list
The parameter list is structured according to the menu branches of the control unit.
For better clarity, the parameters are marked with pictograms.
The parameter is available in the four data sets.
The parameter value is set by the SETUP routine.
This parameter cannot be written in the operation of the frequency inverter.
5.1 Actual value menu (VAL)
Actual values of the system bus
No. Description Unit Display range Chapter
978 Node-State - 1 ... 3 4.12
979 CAN-State - 1 ... 3 4.12
5.2 Parameter menu (PARA)
System bus
No. Description Unit Setting range Chapter
900 Node-ID - -1 ... 63 4.5
903 Baud-Rate - Selection 4.4
904 Boot-Up Delay ms 3500 ... 50000 4.8.4
918 SYNC-Identifier - 0 ... 2047 4.8.2
919 SYNC-Time ms 0 ... 50000 4.9.2
921 RxSDO1-Identifier - 0 ... 2047 4.9.4
922 TxSDO1-Identifier - 0 ... 2047 4.9.4
923 SDO2 Set Active - Selection 4.9.4
924 RxPDO1-Identifier - 0 ... 2047 4.11.1
925 TxPDO1-Identifier - 0 ... 2047 4.11.1
926 RxPDO2-Identifier - 0 ... 2047 4.11.1
927 TxPDO2-Identifier - 0 ... 2047 4.11.1
928 RxPDO3-Identifier - 0 ... 2047 4.11.1
929 TxPDO3-Identifier - 0 ... 2047 4.11.1
930 TxPDO1 Function - Selection 4.11.2
931 TxPDO1 Time ms 0 ... 50000 4.11.2
932 TxPDO2 Function - Selection 4.11.2
933 TxPDO2 Time ms 0 ... 50000 4.11.2
934 TxPDO3 Function - Selection 4.11.2
935 TxPDO3 Time ms 0 ... 50000 4.11.2
936 RxPDO1 Function - Selection 4.11.2
937 RxPDO2 Function - Selection 4.11.2
938 RxPDO3 Function - Selection 4.11.2
939 SYNC Timeout ms 0 ... 60000 4.11.3
941 RxPDO1 Timeout ms 0 ... 60000 4.11.3
942 RxPDO2 Timeout ms 0 ... 60000 4.11.3
945 RxPDO3 Timeout ms 0 ... 60000 4.11.3
946 TxPDO1 Boolean1 - Selection 4.11.5.1
947 TxPDO1 Boolean2 - Selection 4.11.5.1
948 TxPDO1 Boolean3 - Selection 4.11.5.1
949 TxPDO1 Boolean4 - Selection 4.11.5.1
Table continued on next page.