Operating instructions

11/0622
22 11/06
4.9.2 Process SYNC telegram
If synchronous PDO’s have been created in a frequency inverter, their processing is
synchronized with the SYNC telegram. The SYNC telegram is generated by the system
bus master and is a telegram without data.
The identifier is 128 according to the Predefined Connection Set.
If a PC or PLC is used as a master, the identifier of the SYNC telegrams can be adapted
by parameterization on the frequency inverter. The identifier of the SYNC telegram must
be set identically in all nodes on the system bus.
Attention! The identifier range 129 ... 191 may not be used as the emergency tele-
grams can be found there.
The setting of the identifier of the SYNC telegram is done via the parameter
SYNC-
Identifier
918.
Parameter Setting
No. Description Min. Max. Factory setting
918 SYNC-Identifier 0 2047 0
The setting "0” results in identifier assignment according to the Predefined Connection
Set.
The data of the Rx-PDO’s are forwarded to the application after the arrival of the SYNC
telegram. At the same time, the transmission of the Tx-PDO’s with the currently avail-
able data from the application is triggered.
SYNC
SYNC
RxPDO's RxPDO'sTxPDO's TxPDO's
time
This method enables pre-occupancy of set points in the system bus nodes and a syn-
chronous / parallel take-over of the data.