Operating instructions

11/0610
10 11/06
3.3.2 Control terminals
The control and software functionality can be freely configured for economical opera-
tion with a safe function.
Expansion module EM-SYS
0.14 … 1.5 mm
AWG 30 … 16
2
Wieland DST85 / RM3,5
0.14 … 1.5 mm
AWG 30 … 16
2
0.25 … 1.0 mm
AWG 22 … 18
2
0.25 … 0.75 mm
AWG 22 … 20
2
0.2 … 0.3 Nm
1.8 … 2.7 lb-in
Caution! The control inputs and outputs must be connected and separated free of
power. Otherwise, components may be damaged.
The unit may only be connected with the power supply switched off.
Make sure that the frequency inverter is de-energized.
Socket X410B
Ter. Description
1 no function
2 no function
3 no function
4 Earth / GND
5 System bus, CAN low
6 System bus, CAN high
7 PE