Operating instructions
04/08 Application manual Positioning 93
4.8.2.1 Hysteresis for hardware limit switch
Via parameter
Hysteresis 1149, the switching hysteresis of a limit switch (e.g. prox-
imity switch) can be considered. In addition, the hysteresis prevents non-defined
switching when the axis has stopped at a limit switch position.
The drive can be enabled if the distance between the axis and the hardware limit
switch exceeds the value of parameter
Hysteresis 1149.
Parameter Setting
No. Description Min. Max. Fact. sett.
1149 Hysteresis 0 u 2
31
-1 u 182 u
Example:
HW limit switch
F
ormer movement
H
y
steresis
1149
Enable possible
The HW limit switch is activated. The drive can only be enabled after the axis has
been travelled the distance of
Hysteresis 1149 opposite to the former movement.
JOG-Mode can be used to move away from a HW limit switch. Refer to section 4.5
and 4.8.2.3.
Application manual Positioning 9304/08