Operating instructions

04/08 Application manual Positioning 111
In order to avoid oscillations of the drive while it is at standstill, amplification is re-
duced to 50 % of the parameterized value for small position deviations
Ampli
f
ication [%]
Control deviatio
n
of position [°]
0.25-0.25 0.00
50
100
0.50
-0.50
The following behavior may indicate that the controller parameters are not config-
ured properly:
drive is very loud
drive vibrates
frequent contouring errors
inexact control
For the setting options of other control parameters, e.g. speed controller and accel-
eration pilot control, refer to the operating instructions of the frequency inverter.
Note: Optimize the settings in actual operating conditions, as control parame-
ters for speed controller and acceleration pilot control depend on actual
load. Optimize with different load types to obtain a good control behav-
ior in all situations.
Application manual Positioning 11104/08