Specifications

DEUTZ FIRE PROTECTION START-UP AND INSTALLATION CHECK LIST
Page 2of 3
Fire Pump Start up_Aug 28_2007
CHECK LIST
BEFORE ENGINE RUN
Oil level, engine crankcase (see operators manual for
approved oils
& volumes)
Coolant level, (see operators manual for approved coolant &
volumes)
Begin hour meter reading (hrs):
Coolant protection, (Not applicable to oil cooled 2011)
Coolant hoses checked for tightness and proper
installation
Check belt tightness
Air intake system, check tightness, etc.
Exhaust System, check tightness, etc.
Fuel supply and return line connections, check
tightness, etc
Fuel tank full, other
What is hose length from fuel tank to engine.
Fuel suction hose diameter:
Fuel return line diameter:
Prime low pressure side, fuel system
Check external bolts, fittings, coupling, etc.
Describe exhaust system
Total length of pipe
Diameter of pipe
Number of elbows 45
o
90
o
Exhaust back pressure inches of HG
Rain protection: Yes No
Includes flex pipe and supported by building structure:
Yes No
Engine block heater connected to dedicated power
supply: Yes No N/A
DURING ENGINE RUN
Check speed, (RPM):
Check for oil leaks; oil pressure (psi):
Check for coolant leaks
Coolant Temperature (
o
F ):
Coolant loop pressure gauge reading (psi ):
Verify raw water flow (discharge)
Check for external exhaust leaks
Check for fuel leaks
Test High coolant temperature alarm
Test Low oil pressure alarm
Test Over-speed shutdown
Engine gauges functioning properly
AFTER ENGINE RUN
hour meter reading at start of test (hrs): hour meter reading at end of test (hrs):
Stamp start-up date on upper right corner of engine name plate
Review with customer on who to contact for engine parts and service
Customer acceptance of a maintenance contract Yes No Pending
Coolant level full
GENERAL
Room air supply and ventilation equipment complete and adequate. List total dimension of inlet air
opening W x H
List total dimension of discharge air opening W x H
Controller wired per supplier’s instructions, “1” terminal in instrument panel used for cooling water solenoid
Batteries filled, secured and connected:
Cable size:
Total length of battery cable (include pos & neg):
Size of batteries: Number of batteries: