User`s manual
S2000-К
41 www.bolid.com
User’s Code
Entered
ECOD 80 D007
A user has presented
to a reader of the device with
the network address 7 the authenticator #80 regis-
tered by the network controller
Local User’s
Code Entered
ECOD 405(l) D001
A user has presented to a reader of the device
with
the network address #1 the authenticator #405 regis-
tered by the device itself
Device Tamper
Alarm
TA D001
The enclosure of the device with the network
address
1 has been open
Device Tamper
Restored
TR D001
The enclosure of the device with the network address
1 has been closed
Device
Connected
CONNECT D018
The network controller has found the device with the
address 18 within the connected RS-485 interface bus
Device
Disconnected
DISCONNECT D018
Communication between the network controller and
the device with the network number 18 has been lost
:
or the device has been replaced
Device Restarted
RESTART D018
The device with the network address 18 has been re-
started
Power Failure
PWRF D018
The input voltage of the device with the network ad-
dress 18 is out of the normal range
Access
Granted
AG 41 D001
The device with the network address 41 has made a
decision to grant access via its protected door t
o a
user having presented the authenticator #41
Access Denied
AD 41 D001
The authenticator #41 has been read by a reader of
the device with the network address 1, the authentica-
tor being not authorized to gain access to the opera-
tion requested
Illegal Code
ICOD D001
An unknown authenticator has been presented to a
reader of the device with the network address 1
Door Forced Open
DRF D001
The door monitored by the device with the network
address 1 has just been open without granting access
Door Held Open
DRO D001
The door monitored by the device with the network
address 1 has been open for more than a speci
fied
time
Door Closed
DRC D001
The door monitored by the device with the network
address 1
has just been closed after being held open
or forced open
Local
Programming
PROGR D001
The device with the network address 1 has entered
the Key Programming Mode