Arming and disarming are executed when the S2000-K is in the current time display mode, which can
be reached, if necessary, by pressing the CLEAR button. Examples of arming/disarming procedures
using the S2000-K keypad are given below.
Partition Arming Procedure
Switch the S2000-К, if necessary, into the current time display mode
(see above). If the presented authenticator is intended not only to
arm/disarm but also to gain access, press the ON button to switch
the display to the Command Input mode. Type four-digit user
password on the S2000-К keypad or present your electronic access
device to a reader which is assigned to this S2000-K keypad.
If the entered password is not identified by the network controller,
the S2000-K produces the Error beep and displays the ILLEGAL
CODE message followed by switching into the Time Display mode.
After thrice-repeated entering of invalid passwords the keypad
blocks inputting password for 30 seconds.
If the password (access device) is correct, the keypad displays a
status of the first partition accessible to the user (see above). The
example shows partition 1200 being in DISARMED status.
To review the statuses of all accessible partitions scroll the list using
the t and u or type numbers of the required partitions using the
relevant S2000-K buttons.
To arm a partition select it number from the list using the t and u
buttons or enter the number by the keypad numeric buttons, and
then press ENTER.
Menu vARM will appear on the display.
Using the t and u buttons select vARM or vDISARM (if the
user has no rights for arming or disarming, the appropriate menu will
be unavailable). Select vARM and press ENTER.
If arming was successful, the S2000-K produces the Success beep
and displays the new partition status: v1200: ARMED.
Otherwise, the S2000-К will produce the Error beep and display an
error message such as WRONG PARTITION, FAILED or ARMING
FAILED.
In the showed case the zone 003/010 is not armed. Here the 003 is
for the device address into the RS-485 interface and the 010 is the
number of the device’s alarm loop which arming has appeared to be
unsuccessful.
v 1200: DISARMED
vARM
ARM FAIL 003/010
ENTER CODE: