User`s manual

S2000-К Operating
15 www.bolid.com
ARMING AND DISARMING
If the S2000-К keypad is used in a fire and intruder alarm Orion system for authorized arming and/or
disarming specific system partitions, to execute a required operation it is necessary to enter four-digit
user password (PIN code) from the keypad or present the appropriate electronic access device to a
reader which is assigned to this S2000-K keypad. The password or access device should be regis-
tered by the network controller along with a list of partitions authorized for controlling by the given
user and a range of permitted operations such as arming, disarming, both arming and disarming, or
only observing statuses (see the Section Network Controller Setting of this Manual).
If the presented password (or access device) has dual function in the system and is used also for ac-
cess into fixed premises, for switching the keypad into partition control mode before input of the
password (presenting electronic access device) it is necessary to press the ON button (inputting the
password without pressing the ON button in this case will initiate an access request).
After the correct password (electronic access device) is presented, status of one of the user accessi-
ble partitions is represented on the S2000-K display. The partitions can be in following statuses:
DISARMED The partition is disarmed
DISARMING… The partition is being disarmed at the time
ARMED The partition has been armed and being in Norm
ARMING... The partition is being armed at the time
ARMING FAILED The partition failed to be armed
FAULT A fault has been occurred in the partition such as open or short failure in a
some zone
DISCONNECTED Communications with some zones of the partition is lost (e.g., no communica-
tions via RS-485 with the device whose zones are included into the partition)
INTRUSION
ALARM
An Intrusion Alarm in the partition
PANIC ALARM A Panic Alarm in the partition
FIRE PREALARM Fire is supposed to be in the partition
FIRE ALARM There is fire in the partition