User`s manual
S2000-К Operating
13 www.bolid.com
ACCESS REQUESTS
When the S2000-К keypad is used in an access control system, to request access into protected
premises it is necessary to enter four-digit password (PIN code) which must be registered by the net-
work controller with appropriate privileges. User identification can be made also by means of a Touch
Memory device (iButton) or Proximity card registered by the network controller with appropriate privi-
leges and presented to one of the Orion ISS reader which is assigned to this S2000-K keypad (see
the Network Controller Setting section of this Manual).
For authenticators (that is, electronic access devices and contactless cards) that give the rights of
passage through several access points it is necessary to specify the number of the door which is to
be opened.
If the presented authenticator is recognized by the network controller and gives access rights for pas-
sage through the specified door, the S2000-К displays the ACCESS GRANTED message, and the
network controller sends a command for the relevant executive device to unlock the door.
Otherwise the S2000-К gives an Error signal and displays an access reject message with specifying
one of the reasons as follows:
ILLEGAL CODE The authenticator presented is not registered by the network controller
ACCESS DENIED The authenticator presented has no authorities to gain access via the
specified door or access is blocked for this one
WRONG PARTITION The authenticator presented has no authorities to gain access to the
specified partition
FAILED Command run error
Requesting access is carried out from the S2000-K quiescent mode, which can be reached if neces-
sary by pressing the CLEAR button. Examples of access request using the S2000-K keypad are giv-
en below.
Request with the Rights to Access through a Single Door
Switch the S2000-К if necessary into the Time Display mode (see
above) and type your four-digit password on the S2000-K keypad
(or present your electronic access device to a reader which is
assigned to this S2000-K).
In success case the positive access message will be displayed on
the S2000-K LCD, and the beeper will produce the Success signal.
Otherwise, the beeper will produce the Error audible signal, and an
access reject message will be indicated by the display.
After thrice-repeated entering of invalid passwords the keypad
blocks input for 30 seconds.
ENTER CODE:
ACCESS GRANTED