User`s manual
Orion ISS
www.bolid.com 92
Self-Diagnostic Test
WARNING! Disconnect if necessary all locking units before testing the S2000-2
controller in self-diagnostic mode
To start self-diagnostic test remove the top cover of the controller enclosure and make three short and
one long pressing on the tamper switch. ‘Short pressing’ means ‘press and held the tamper switch
pressed for 0.1 - 0.5s’, while ‘long pressing’ means ‘press and held the tamper switch pressed for at
least 1.5s’. Pauses between pressings must not exceed 0.5s.
The test outcome is considered as success if the sequence pressings said above causes the control-
ler behavior as follows:
− The READY indicator flashes rapidly
− The controller sounder plays two beeps
− The LED 1 and LED 2 of the controller lights in turns with red for 1s and green for 1s.
− The contacts of the relay 1 are closed together with LED 1 switching on, the contacts of the re-
lay 2 being closed together with LED 2 switching on.
Condition Inspection of Readers’ Connection Circuits
Inspect the condition of readers’ circuits by doing the following:
1. Present an unknown access key to the first reader of the S2000-2. The red LED 1 of the
S2000-2 and the red LED of the reader must flash three times. The internal sounder of the
S2000-2 and the reader sounder, if used and controlled, must play long ‘Error’ beep each.
2. Repeat the said procedure for the second reader of the S2000-2.
If the S2000-2 controller doesn’t respond upon a key presenting it can be caused by mismatching of
the reader data format and the set value of reader’s Output Interface type (which is Touch Memory by
default − see Reader Configuration Parameters Section of this Manual).
If a long beep is not heard it can indicates that the sound signaling is disabled for the controller or the
reader (it is enabled by default − see Reader Configuration Parameters Section of this Manual).