User`s manual

S2000-2 S2000-2 Programming
85 www.bolid.com
PROGRAMMING THE CONTROLLER DEPENDING ON ITS OPERATION MODE
Two Entrance Doors Mode Programming
In order to program the S2000-2 controller for operating in Two Entrance Doors mode by means of
UProg Configuration Tool:
1. Select the ‘Two Entrance Doors’ value in Operation Mode field on the Device tab.
2. If door sensors are in use set the relevant Passage Sensor flags on, else unset them.
3. If any mechanical or electrical buttons, as well as any other equipment, are used to open the
lock without participation of the controller, the Forced Open Monitoring and Held Open Moni-
toring parameters are to be unset in order to avoid false alarms.
4. If electric strikes are in use as locking units, set for each relay (the Outputs tab)
‘Switch On for a Time’ in Executive Program field
1 ÷ 5s in the Relay Activation Time field (the time sufficient for the strike to be actuated)
‘Switch off after door being opened’ flag (for the strike to be cocked properly upon quick
passing)
Please note that Free Pass Access mode can not be implemented for an access point if the
electric strike is used as a locking unit.
If magnet locks are in use as locking units, set for each relay (the Outputs tab)
‘Switch Off for a Time’ in Executive Program field
5 ÷ 20s in the Relay Activation Time field (maximum passage time)
‘Switch off after door being opened’ or ‘Switch off after door being closed’ flag (for the lock
to be secured just after a passage detection)
5. For all access groups (the Access Groups tab) Anti-passback Mode field must be set to
‘None’.
6. Entry Mode parameters on the Access Groups tab in the UProg is interpreted by the controller
as the mode for passing in forward direction via the first door, Exit Mode being interpreted as
the mode for passing in forward direction via the second door.
7. Programming time zones on the Time Zones tab in UProg, select Entry and Exit interval activ-
ity considering an entry interval to be the interval to gain access in forward direction via the
first door and an Exit interval to be the interval to gain access in forward direction via the sec-
ond door.
Other configuration parameters are adjusted depending on specific user needs and desires.