User`s manual
Orion ISS
www.bolid.com 78
Parameter Function Description Value Range
Entry Mode
Defines the rules to access the zone with the
specified number (zone controlled by the first
reader of the S2000-2) for owners of the keys of
the programmed access group
Locked
Simple
Confirmation Only
Two-person Rule
Three-person Rule
Exit Mode
Defines the rules to access the zone with the
specified number (zone controlled by the second
reader of the S2000-2) for owners of the keys of
the programmed access group
Locked
Simple
Confirmation Only
Two-person Rule
Three-person Rule
First Access Group
to Confirm Entry
The number of an access group assigned with the
key which must be presented after the presenting
the key of programmed access group in order to
confirm access rights if the Entry Mode is set to
Two-person Rule
0…32
Second Access
Group to Confirm
Entry
The number of an access group assigned with the
key which must be presented after the presenting
of two relevant keys (see above) in order to con-
firm access rights if the Entry Mode is set to
Three-person Rule
0…32
First Access Group
to Confirm Exit
The number of an access group assigned with the
key which must be presented after the presenting
the key of programmed access group in order to
confirm access rights if the Exit Mode is set to
Two-person Rule
0…32
Second Access
Group to Confirm
Exit
The number of an access group assigned with the
key which must be presented after the presenting
of two relevant keys (see above) in order to con-
firm access rights if the Exit Mode is set to Three-
person Rule
0…32
Arm/Disarm
Defines that keys assigned with the access group
configured are designed to arm and disarm the
alarm loops of the S2000-2 controller
On/Off
Time Schedule
(Arming/Disarming)
The number of a time schedule specifying the
time zones when the arming/disarming is permit-
ted for the owners of keys included in the access
group programmed
0…16
Arm Loop 1
On/Off
Arm Loop 2
Setting of these switches on permits arming of the
specified alarm loops of the S2000-2 for all the
keys included to the access group
On/Off
Disarm Loop 1
On/Off
Disarm Loop 2
Setting of these switches on permits disarming of
the specified alarm loops of the S2000-2 for all
the keys included to the access group
On/Off
Entry Mode (Exit Mode) parameter defines conditions necessary for access to the zone controlled by
the first reader (the second reader) to be granted.
For the Simple entry (exit) mode it is sufficient to present only one user access key.