The maximum time of the relay activation while granting access is given by the Relay Activation
Time parameter. The maximum relay activation time can reach 2h 16min 31.875s, the incremental
step being 0.125s.
For all the controller operation modes a standard time period is provided for passing after access is
granted. If no passage is detected within this time (the door sensor in the door control circuit was not
activated) the access will be regarded as not used and the identification procedure has to be re-
peated. If the Relay Activation Time has not expired to the moment of expiration the passage time,
the passage time is prolonged up to the moment when the relay returns to its initial condition. So the
maximum time the system waits for a passage can be prolonged if the Relay Activation Time exceeds
the standard passage time (of cause if the locking unit being in use supports applying such a long
opening signal).
If the Switch Off After Door Being Opened attribute is set for the relay and access is granted, the
relay will return to its initial condition immediately after the door has been opened (the passage sen-
sor has actuated) before elapsing the Relay Activation Time.
If the Switch Off After Door Being Closed attribute is set for the relay and access is granted, the
relay will return to its initial condition after the door is open and then has been closed again (the pas-
sage sensor has been restored) before elapsing the Relay Activation Time.
If none of these attributes is set, the relay will always be switched on (off) strictly for the Relay Activa-
tion Time (except for the Swing-beam Barrier operation mode see Swing-beam Barrier Mode Sec-
tion of this Manual).