For Two Entrance Doors, One Entrance/Exit Door and Turnstile modes, after granting the ac-
cess the controller is waiting for a passage to be detected (the door to be open, the turnstile to
be rotated and so on) for the Relay Activation Time, but at least for 10 seconds. Before sensing
the passage or this time having been expired the controller ignores all attempts to present iden-
tifiers to the reader again
When the sensor has just actuated the PASSAGE message is generated by the controller
Monitoring the door for held or force open has been available (see the description of the Forced
Open Monitoring and Held Open Monitoring parameters)
The relay which controls the lock can be switched off lock before the Relay Control Time hav-
ing been expired (see the description of the Switch Off After Door Being Opened and Switch
Off After Door Being Closed parameters)
If the Passage Sensor parameter is unset, the mentioned above functions are unavailable, passing is
not expected and in the Two Entrance Doors, One Entrance/Exit Door and Turnstile modes the sys-
tem indicates the fact of access granting by means of the reader LED, which is switched on for the
Relay Activation Time, but at least for 2 seconds.
If the Forced Open Monitoring parameter is set, door opening preceded by no access granting will
cause the DOOR FORCED alarm message to be generated and the light and sound alarms to be
activated.
If the Held Open Monitoring parameter is set, door being opened for more than Held Open Timeout
will cause the DOOR LEFT OPEN alarm message to be generated and the light and sound alarms to
be activated.
The LED Control Polarity parameter defines the active logic level to control red and green LEDs of
the reader. If the Forward control polarity is set, the high logic level is used to activate the LEDG and
LEDR of the controller. If the Reverse polarity is selected, the LEDs will be activated by low logic
level.
It is advisable to set this parameter to
¾ Forward (1 active) for IButton readers and for most readers with Wiegand interface,
¾ Backward (0 active) for most readers with Touch Memory interface (except iButton readers)
The Sounder Control Polarity parameter defines the active logic level to control the sounder of the
reader similarly to those of the LED Control Polarity.
It is advisable to set this parameter to
¾ Forward (1 active) for most readers with Wiegand interface,
¾ Backward (0 active) for most readers with Touch Memory interface