User`s manual

S2000-2 Installation
63 www.bolid.com
Connecting Readers with Wiegand Output Interface
D1
LEDG
GND
S2000-2
LEDR
+12V
BEEP
D1
LEDG
GND
Reader
LEDR
+12V
BEEP
D0
LEDG
GND
S2000-2
LEDR
BEEP
D0
LEDG
GND
Reader
LEDR
+12V
BEEP
0V
RIP-12
+12V
D0 D0
D1 D1
Variant 1
is intended for readers with current
consumption not exceeding 100 mA and
located within 50m from the controller
Variant 2
is intended for readers with high current
consumptions or far from the controller more
than 50m
1) If a reader is equipped with a single LED control circuit this circuit is to be connected to the
LEDG terminal of S2000-2, with LEDR terminal being left unconnected
2) If a reader is equipped with no built-in sounder the BEEP terminal of the S2000-2 controller is to
be left unconnected
Figure 14. Reader with Wiegand Output Interface Wiring Diagram
Connecting Readers with ABA TRACK II Output Interface
Readers with the ABA TRACK II magnet cards interface are connected similarly to the readers with
the Wiegand interface. The DATA output of the reader is connected to the D0 input of the controller
and the CLOCK output of the reader is connected to the D1 input of the controller.
Connecting an Arming Request Button
If combined keys designed both for access and arming/disarming are supposed to be presented to a
reader the Arming Request button is to brought to the reader circuit as shown in Figure 15.
S2000-2
GND1(GND2)
D0-1(D0-2)
1
3
XT2(XT3)
Armin
g
Re
q
uest Button
To a Reader
Figure 15. Arming Request Button Wiring Diagram