User`s manual

Orion ISS
www.bolid.com 42
LIGHT AND SOUND ALARMS
The S2000-2 controller transmits signals to its built-in LEDs and sounder, as well as to LEDs and
sounders of the readers.
READY LED indication is shown in Table 2.
The indication of reader LEDs is similar to that of the 1 and 2 controller LEDs and is shown in Table 3.
The behavior of reader sounders is similar to the behavior of the S2000-2 sounder and is shown in
Table 4.
Table 2 READY LED Indication
S2000-2 Condition/Event READY LED Behavior
Quiescent mode On
Power fault (the supply voltage is out of
normal range)
Flashes twice per second
Programming a Master key Double short flashes with long pauses
Test mode Flashes 5 times per second
Table 3 Reader LED and Controller 1 and 2 Indication
Condition/Event Lighting Mode Color
LED standby mode – 1 (off) Off
LED standby mode – 2 or 3
(loops are armed)
On if the loops are armed
Off if they are disarmed
Red
Quiescent
mode
(controlled
access mode
with no
alarms)
LED standby mode – 4 (red lit) On Red
Access Locked mode On with short pauses Red
Free Pass mode On with short pauses Green
Access is granted and a passage is expected On Green
A Main code is recognized, no access violations,
an Additional code reading is expected
Flashes 5 times per second Green
A Confirmation code reading is expected (two
person access rule)
Flashes 5 times per second Green
Access is denied Three rapid flashes Red
The key presented is not known to the S2000-2
controller and the decision of the network con-
troller is expected
Flashes with red and green
alternately 5 times per second
Red/Green
Loop alarm
*
Flashes twice per second Red
Loop arming fault
*
Flashes twice per second Green