User`s manual

S2000-2 Operating
39 www.bolid.com
Table 1 Partition Status Indication
Partition Status Reader Indicator Behavior Indication Color
Disarmed Off
Armed On Yellow (green + red)
Intrusion Alarm
Fire Alarm
Fire Prealarm
Arming Failed
Blinks 2 times per second Yellow (green + red)
Trouble (in a fire partition) Flashes once for a second Yellow (green + red)
If the key unknown to the S2000-2 is presented to one of its readers when the communications be-
tween the controller and the network controller is lost, the ACCESS DENIED message is generated.
This message (as well as the other ones) is kept in non-volatile memory of the S2000-2 controller,
being sent to the network controller as soon as the connection is restored.
If a combined key (for centralized access + partition control or local access + partition control) is pre-
sented, it is considered as the key for access request (see below). In order to arm/disarm partitions
(alarm loops) remotely by means of this key presenting, the controller has to be switched to Ready to
arm/disarm mode, similarly to it is performed when combined keys are used for the local arm-
ing/disarming of alarm loops (see Alarm Loop Arming/Disarming and Alarm Loops Sections of this
Manual).
The centralized access and partition control are disabled upon the RS-485 communication faults.
If the Orion system operates under an ARM Orion Pro Workstation of versions 1.11+, such features
as two-factor authentication and two (three) person rule access are supported for the centralized ac-
cess.