User`s manual

S2000-2 Operating
27 www.bolid.com
armed partition will be armed, and vice versa). The condition of the partition is indicated by the reader
LEDs within 30 seconds or until another identifier is presented.
When the EXIT button is pressed, access is granted, but the ACCESS GRANTED message is gener-
ated without indicating a key code (impersonal).
If the door sensor (passage sensor) is actuated within the standard time to pass or within the relay
activation time (whichever is longer), the PASSAGE message is generated, otherwise the access is
considered to be not used, and the controller starts waiting for next access procedure to begin. In the
both cases (actual passage detection or timeout expiration) the green LED is shut off and the reader
LED is switched to the normal mode (which can be off, red light or loop condition indicating).
Alarm Loop Arming/Disarming
In order to arm/disarm alarm loops by a key intended only for this purpose (namely, a key of User
type, assigned to an access group with Arming/Disarming flag set on and Access flag unset see
Access Group Parameters Section of this Manual), this key is to be presented to any reader of the
controller.
The controller will check if the key record exists in the controller database, is authorized to control the
loops, if key time zone is active for the current time and all access conditions are met (if two-factor
authentication is applied to the reader an additional code also has to be presented).
If the key is authorized to control alarm loops of the controller, and all these alarm loops are disarmed,
they will be armed. Otherwise these loops will be disarmed.
When the loop is being armed, the LED of the reader is switched on for 2 seconds (yellow color).
When the loop is being disarmed the LED is switched off for 2 seconds.
In order to arm/disarm loops by means of combined keys (access + arming/disarming, access unlock-
ing + arming/disarming, access locking + arming/disarming) the controller is to be preliminary
switched to special Ready to Arm/Disarm mode. For this purpose the Arming Request button has to
be pressed (see Figure 15) and held pressed for at least 1s, until the reader’s LED starts flashing rap-
idly. Instead of using the Arming Request button, both terminals of the iButton reader can be coupled
for the same time. After that, while the reader’s LED is flashing (20s), the combined key will be inter-
preted by the controller as arming/disarming request.
If the reader has Touch Memory output interface, in order to arm/disarm loops it is sufficient to hold
the combined key presented to the reader within a Time to Hold Keys for Arming/Disarming time pe-
riod. In this case it is not obligatory to switch the controller to the Ready to Arm/Disarm mode. When
the card, for example, is held near the reader, the LED flashes with yellow 4 times per second, and
after this time has been expired the relevant loop is armed (reader LED is switched on for 2 seconds)
or disarmed (reader LED is switched off for 2 seconds). If the card is taken from the reader before the
Time to Hold Keys for Arming/Disarming time is expired, the main function of the combined card is
realize: the access is granted, unlocked or locked.