Trimetric Cable Wiring Diagram
2 feet stripped
a few inches #14 wire.
Fuseholder with 1A fast blow fuse (3AG size)
Red
Black
Black
white
Unstripped
(TriMetric end)
Unstripped
(TriMetric end)
3/8 clearance ring
connector
3/8 clearance ring
connector
5/32 clearance ring
connectors
5/32 clearance ring
connectors
Maximum length of cable from
TriMetric to Battery:
With #22 gauge: up to 100 feet.
With #18 gauge: up to 300 feet.
With #18 gauge, up to 500 feet is ok if
another wire is paralleled with G1.
Maximum length of cable from
TriMetric to Battery:
With #22 gauge: up to 100 feet.
With #18 gauge: up to 300 feet.
With #18 gauge, up to 500 feet is ok if
another wire is paralleled with G1.
TO + Terminal
on battery.
TO + Terminal
on battery.
(2 blacks) to KELVIN
terminal away from
minus ( ) terminal of
battery.
-
(2 blacks) to KELVIN
terminal away from
minus ( ) terminal of
battery.
-
(White) to KELVIN
terminal nearest
minus ( ) terminal
of battery.
-
(White) to KELVIN
terminal nearest
minus ( ) terminal
of battery.
-
White
Black
Black
Red
Long length of 4 or 6
conductor cable from
TriMetric to battery.
Long length of 4 or 6
conductor cable from
TriMetric to battery.
Instructions for connecting
cable to TriMetric end:
1. Find black paired with white:
2. Connect black paired with white to G2.
3. Connect white to SIG.
4. Find black paired with red
5. Connect black paired with red to G1.
6. Connect red to +.
Instructions for connecting
cable to TriMetric end:
1. Find black paired with white:
2. Connect black paired with white to G2.
3. Connect white to SIG.
4. Find black paired with red
5. Connect black paired with red to G1.
6. Connect red to +.
NOTES FOR CONNECTING TRIMETRIC TO BATTERY AND SHUNT
BOGART ENGINEERING 04/18/12
STEPS FOR CONNECTING CABLE FROM
TRIMETRIC TO BATTERY.
1. Remove fuse from fuseholder (below).
2. Connect 4 wires as shown (below) at shunt/battery end.
3. Connect 4 wires as shown to the TriMetric terminal block as
described (right) on this sketch.
4. Make a final check of the wiring.
5. Install fuse in fuseholder. TriMetric digits should light.
Also refer to diagram in TriMetric (Part 1)
instructions, last page.
STEPS FOR CONNECTING CABLE FROM
TRIMETRIC TO BATTERY.
1. Remove fuse from fuseholder (below).
2. Connect 4 wires as shown (below) at shunt/battery end.
3. Connect 4 wires as shown to the TriMetric terminal block as
described (right) on this sketch.
4. Make a final check of the wiring.
5. Install fuse in fuseholder. TriMetric digits should light.
Also refer to diagram in TriMetric (Part 1)
instructions, last page.
SIG
G2
G1
+
Designations on TriMetric terminal blockDesignations on TriMetric terminal block
TriMetric end
Battery/shunt end