TM-2030 Installation & User Guide
Advanced Programmable Parameters
Programming Instructions for the TM-2030: http://www.bogartengineering.com/wp-content/uploads/docs/EnterP1Data.pdf
Refer to SC-2030 instructions for programmable parameters when using the SC-2030 Solar Charger (P8-P14-P15-P16-P20-P21-P22)
P8-P22 are accessible only when Program P7 is set to L3 or L4. Default values shown below are automatically installed when switching from L4 or L3 into
L2 or L1.
P9: Lo-battery audible alarm: based on % full and battery voltage. Set “low % full” alarm point with P9 (OFF, 1-100%). Default “OFF”.
P10: Efficiency factor (60-100%): This parameter affects how the “% full” is evaluated. Discharging amp-hours always evaluated at 100%. Charg-
ing amp-hours evaluate at an amps rate determined by this setting. This compensates for battery charging inefficiency. The default and recom-
mended value is 94%
P11: Shunt type: Set to “H” for 500A/50mV. Set to “L” for 100A/100mV. Default H. Also use “H” when using a 1000 A-100 mV shunt (rarely used)
P12: Auto Reset ON-OFF: When OFF percent full and amp hours are not automatically reset. Default ON
P13: Low battery voltage alarm setting: “low threshold volts” (10.0-65.0 V) Default: 10.0 Audible alarm also controlled by P9 .
P17: Shows how many hours after “now” that daily history data H7, H8 ,H9 will be recorded: (0-24). Default 12
P18: Battery calibration voltage adj. Not recommended unless advised by Bogart Engineering.
See TM-2030 User’s Instructions, Section 6.4.
P19: Resets TriMetric to factory default settings.