Operating instructions
22
EN
17: Inverter C voltage adjustment
Interface Setting
Parameter 2: you may choose Add or Sub to adjust inverter C
voltage*.
Parameter 3: the voltage range is from 0V to 9.9V, the default
value is 0V.
*It will display number 2 under
or to represent
inverter C voltage.
18: Output A voltage calibration
Interface Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3: it shows the internal measurement value of the
output A voltage, and you can calibrate it by pressing Up or Down
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing Enter
. The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.
19: Output B voltage calibration
Interface Setting
Parameter 2: it always shows OP.V as output voltage*.
Parameter 3:
it shows the internal measurement value of the
output B voltage, and you can calibrate it by pressing Up or Down
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing Enter
. The
calibration range is limited within +/-9V. This function is normally
used for parallel operation.
*It will display number 1 under to represent the output B
voltage.
20: Output C voltage calibration
Interface Setting
Parameter 2: it always shows OP.V as output voltage.
Parameter 3:
it shows the internal measurement value of the
output C voltage, and you can calibrate it by pressing Up or
Down
according to the measurement from an external voltage
meter. The calibration result will be effective by pressing Enter.
The calibration range is limited within +/-
9V. This function is
normally used for parallel operation.
*It will display number 2 under to represent the output C
voltage.