3-6. LCD Setting
There are three parameters to set up the UPS. Refer to following diagram.
Parameter 1: It’s for program alternatives. Refer
to below table for the programs to set up.
Parameter 2 and parameter 3 are the setting
options or values for each program.
Note: Please select “Up” or “Down” button to
change the programs or parameters.
Programs available list for parameter 1:
Code
Description
Bypass
AC
CVCF
Battery
Battery Test
01
Output voltage
Y
02
Output frequency
Y
03
Voltage range for bypass
Y
04
Frequency range for bypass
Y
05
Reserved
06
Reserved
07
Reserved
08
Bypass mode setting
Y
Y
09
Battery maximum discharge time setting
Y
Y
Y
Y
Y
10
Reserved
11
Reserved
12
Reserved
13
Battery voltage Calibration
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
15
Inverter voltage Calibration
Y
Y
Y
16
Reserved
17
Reserved
18
Charger maximum current setting
Y
Y
Y
Y
Y
Parameter 1
Parameter 2
Parameter 3