User`s guide

11.8.5 Connecting an analog gauge or source (4-20mA) to the
modem’s analog input:
Figure 28
Follow the above diagram to convert a 4-20mA source into a 0-5Vdc input to the modem’s
analog input (ADC). 249 and 255 ohms are standard values for a 1% resistor.
Readings:
At 20mA, the modem reads around 5V on the analog pin
At 4mA, the modem reads around 1V
When the current loop is missing, the modem reads 0V
11.9 Mounting the modem
The modem requires four #4 screws (3/16”) pan or fillister head, as well as corresponding lock
washers.