User`s guide

4000 & 5000 Series User’s Guide
2.3.2 I/O Specifications
The modem has 4 digital inputs, 3 analog inputs and 3 digital outputs for remote control and
monitoring. The third digital output (O3) is located on the power connector for all modems.
The third analog input (AI3) is not available on the 4200/5200 models.
AI2 GND
AI1 AI3
O2 DI2
O1 DI1
DI4
DI3
Figure 2 – I/Os (Looking at back of modem)
3x Digital Outputs (O1, O2, O3) – O3 available on Power connector
Configuration Open Collector, reference to ground
Absolute Maximum IDC 500mADC (Vce = 750mVDC)
Absolute Maximum VDC 30VDC (open circuit)
Absolute Minimum VDC 0.4VDC (open circuit)
4x Digital Inputs (DI1, DI2, DI3, DI4)
Configuration Non-isolated level detection, reference to ground
Active level 1.6VDC to 30VDC
Inactive level 0VDC to 1.3VDC
Absolute Minimum VDC 0.3VDC
Absolute Maximum VDC 33VDC
Leakage IDC at 5VDC 150uADC
3x Analog Inputs (AI1, AI2, AI3) – AI3 only available on 4600/5600
Configuration Not isolated input, reference to ground
Resolution 1024 (ADC 10-bit)
VDC per step 4.8875855mVDC
Full scale level 5VDC
Zero level 0VDC
Absolute Minimum VDC -0.3VDC
Absolute Maximum VDC 8.3VDC
Leakage IDC at 5VDC 265.96 uADC TYPE
Table 4
Revision 1.5 Copyright © 2007 BlueTree Wireless Data Inc. Page 11 of 67