Oil Furnace L85 Series Installation Manual
Table Of Contents
507148-01 Issue 1406 Page 5 of 13
Vertical Venting
1. Local building codes may have more stringent
installation requirements and should be consulted
before installation of the unit.
2. The ue pipe should be as short as possible to do the
job.
3. The ue pipe should not be smaller than the outlet
diameter of the ue outlet of the furnace.
4. Single wall ue pipe should not run outside or through
any unconditioned space.
5. The chimney should terminate 2’ above the highest
peak of a peaked roof, and 3’ higher than a at roof.
6. The ue pipe must not pass through a oor or ceiling.
Clearances to single wall ue pipe should be no less
than specied in Table 1.
7. The ue pipe may pass through a wall where provisions
have been made for a thimble as specied in the
Standards of the National Board of Fire Underwriters
(see Figure 2).
Figure 2. Wall Thimble
Thimble
Flue Pipe
CombustibleWall
8. The ue pipe should slope upward toward the chimney
on a horizontal run of at least 1/4” per foot and should
be supported by something other than the furnace
(see Figure 3 and Figure 4).
9. Extend the ue pipe into the chimney so that it is ush
with the inside of the ue liner. Seal the joint between
the pipe and the liner.
10. The furnace shall be connected to a factory-built
chimney or vent complying with a recognized standard,
or a masonry or concrete chimney lined with a lining
material acceptable to the authority having jurisdiction.
11. When two or more appliances vent into a common
ue, the area of the common ue should not be less
than the area of the largest ue or vent connection
plus 50% of the areas of the additional vents or ue
connections. The chimney must be able to suciently
vent all appliances operating at the same time.
12. The ue pipe shall not be connected to a chimney ue
serving a solid fuel appliance or any mechanical draft
system.
13. All unused chimney openings should be closed.
Figure 3. Factory-Built Chimney
Rear Flue
Barometric Control
(in either location)*
Factory-Built
Chimney
Drain for
Condensate
Factory-Built
Chimney
Barometric Control
(in either location)*
Drain for
Condensate
* Barometric control may be installed in either the vertical or
horizontal section of the ue pipe within 18” of the ue outlet of
the furnace.
Front Flue
14. All vent pipe run through unconditioned areas or
outside shall be constructed of factory-built chimney
sections (see Figure 3).
15. Where condensation of ue gases is apparent, the vent
shall be constructed to prevent the condensation from
entering the ue transition box opening. Provisions
shall be made to drain o the condensate (see Figure
3).
16. Vent connectors serving this appliance shall not be
connected into any portion of a mechanical draft
system operating under positive pressure.
17. Keep the area around the vent terminal free of snow,
ice, and debris.