OIL FURNACE START-UP CHECKLIST
(Complete this page and keep for future reference)
Customer Name
Address
City State Zip Code
Furnace Model # Serial #
Input Rate Nozzle Used
New Construction Replacement
Date of Installation
Installation Data Start-Up Procedure
Furnace Location: A. Close disconnect switch
A. Basement - Open Enclosed* B. Set thermostat to call for heat
B. Utility Room - Open Enclosed*
C. Bleed air from lines and pump; run for 20
seconds after bubble disappears
C. Closet - Open Enclosed* D. Install vacuum gauge; check pump vacuum
D. Crawlspace - Open Enclosed* E. Install pressure gauge; adjust pressure to 145 or 150 psig
* Provisions must be made for adequate air for combustion. See Combustion and
Ventilation Air on page 3.
Always verify proper pump pressure to corresponding
tables with instructions supplied with unit.
Chimney Data: F. After 10 minutes of operation, obtain ue temperature reading:
A. Inside Outside 1st 2nd 3rd
B. Brick or Masonry G. Obtain smoke reading
C. Lined Size 1st 2nd 3rd
D. Type: Class A All-Purpose Type L H. Measure CO
2
E. Condition 1st 2nd 3rd
Flue Pipe: I. Check draft overre Breech
A. Distance to chimney Pitch J. Air shutter setting Locked
B. Diameter K. Measure static pressure in duct system
C. Barometric damper installed
Static pressure on supply side
D. Drill 5/16” hole in ue pipe 12” upstream of barometric damper Static pressure on return side
E. Obtain drafting reading; adjust barometric Static pressure drop
Oil Tank Data:
L. Temperature rise after steady state conditions have been
achieved
A. Installed in basement Supply side Return side
B. Outside
M. Block o return air (limit control checkout);
burner should shut down in 2 or 3 minutesC. Buried / Depth
D. Size gallons
E. Age Owner Record
F. Date of last cleaning Installed by:
Oil Lines: Dealer
A. Size: 3/8” 1/2” Other Address
B. Single pipe Two pipe
C. Distance from tank Lift
D. Filter type Inspect Change Telephone #
E. Pressure test License #
F. Recheck all ttings for tightness
Thermostat:
Manufactured By
Blue Summit LLC
8201 C National Turnpike
Louisville, KY 40214
A. Type: Heating Cooling
B. Anticipator set
C. Wires: New Old
Air Filter:
A. Type: Permanent Disposable
B. Installed
C. Size
These checks or tests are required for all oil units.