BMKH MFCC user manual
Table 2
(1). The connecting pipe should be thermally insulated properly.
(2). The pipe wall thickness shall be .019-.039 in and the pipe wall shall be
able to withstand the pressure of 6.0 MPa. The longer the connecting pipe, the
lower the cooling and heating effect performs.
(3).The pipe wall thickness shall be .019-.039 in and the pipe wall shall be able
to withstand the pressure of 6.0 MPa. The longer the connecting pipe, the
lower the cooling and heating effect performs.
Item
Model
Size of Fitting Pipe(Inch)
Max.
Pipe
Length
(m)
Max. Height
Difference
between Indoor
Unit and Outdoor
Unit (m)
Indoor unit
Drainage
pipe(Outer
Diameter ×
wall thickness)
(in)
Liquid Gas
BMKH09MFCC
BMKH12MFCC
1/4 3/8 65 32 Φ17×0.068
1/4 1/2
65 32 Φ17×0.068
BMKH18MFCC
1/4 1/2 65 32 Φ17×0.068
BMKH24MFCC
3/8 5/8
65 32 Φ17×0.068
.4 Electrical Requirement
Electric Wire Size and Fuse Capacity.
Table 3
Notes:
①
. The fuse is located on the main board.
②
. Install the disconnect device with a contact gap of at least 3 mm in all poles
nearby the units (Both indoor unit and outdoor unit).The appliance must be
positioned so that the plug is accessible.
③
. The specifications of the power cable listed in the Table above
are determined based on the maximum power (maximum amps)
of the unit.
④
. The specifications of the power cable listed in the Table above are applied to
the conduit-guarded multi-wire copper cable (like, YJV copper cable,
consisting of PE insulated wires and a PVC cable jacket) used at 40°С(104°F) and
resi
stible to 90°С(194°F) (see IEC 60364-5-52). If the working condition changes,
they should be modified according to the related national standard.
Indoor Units
Power Supply
Fuse
Capacity
Min. Power
Supply Cord
V/Ph/Hz A
2
9~24k
208/230V~
60Hz
5 18AWG(0.82mm )
14
Floor Ceiling Type Unit