BE5E Specifications Sheet

COMPACT AIR HANDLER BCE5E
Page 2
MODEL NUMBER GUIDE
REVISION NUMBER
50 = OMNIGUARD COIL
METERING DEVICE
4X = R410A TXV
VOLTAGE
A = 208/230V - 1 PHASE - 60HZ
POSITION
M = MULTI-POSITION
TONNAGE
24, 30, 36, 42, 48, 60
PRODUCT
BC= BLOWER COIL
FEATURE SET
E = ENHANCED FEATURES
SERIES
5 = 5 SERIES (1 PIECE PLATFORM,
OMNIGUARD
TM
)
MOTOR & CONTROL
C = PSC
E = CONSTANT TORQUE
V = VARIABLE SPEED
BC E 5 E 24 M A 4X - 50
PHYSICAL
Model Volts/Hz/Phase
Max. Elec.
Heat (kW)
Transformer
Size & Type
Filter Size
(in.)
Refrigerant Connection
Installed
TXV Size
Weight
(lbs.)
Suction (in.) Liquid (in.)
BCE5E24 208-230/60/1 10 40 VA Class 2 15 x 20 3/4 3/8 H4TXV01 127
BCE5E30 208-230/60/1 15 40 VA Class 2 15 x 20 3/4 3/8 H4TXV01 133
BCE5E36 208-230/60/1 15 40 VA Class 2 18 x 20 7/ 8 3/8 H4TXV02 163
BCE5E42 208-230/60/1 15 40 VA Class 2 18 x 20 7/8 3/8 H4TXV02 168
BCE5E48 208-230/60/1 20 40 VA Class 2 18 x 20 7/8 3/8 H4TXV02 186
BCE5E60 208-230/60/1 20 40 VA Class 2 18 x 20 7/8 3/8 H4TXV03 186
Cabinet 0 in. (0 mm)
To Plenum 0 in. (0mm)
To Outlet Duct within 3 ft. (914mm) 0 in. (0 mm)
Floor 0 in. (0 mm) See Note #1
Service / Maintenance See Note #2
1 Units installed on combustible floors in the downflow position with electric heat require optional downflow combustible flooring base.
2 Front service access - 24 in. (610 mm) minimum.
Note - If cabinet depth is more than 24 in. (610mm), allow a minimum of the cabinet depth plus 2 in. (51 mm).
INSTALLATION CLEARANCES WITH ELECTRIC HEAT