507788-01B Issue 1818 Page 15 of 20
Blower Performance Data
Speed
Tap
Application
External Static Pressure (in. w.c.)
0.1 0.2 0.3 0.4 0.5
-24
1 Fan Only 590 575 530 480 430
2 Matched with 1.5 ton condensing unit 750 650 610 550 480
3 Nominal 2 ton match without electric heat 950 825 785 740 690
4 Nominal 2 ton match with electric heat 1040 1020 985 940 920
5 High static application 1160 1140 1120 1080 1050
-30
1 Fan Only 700 665 625 565 490
2 Matched with 2 ton condensing unit 860 810 770 715 665
3 Nominal 2.5 ton match without electric heat 1040 1010 980 940 890
4 Nominal 2.5 ton match with electric heat 1140 1100 1045 1015 980
5 High static application 1390 1375 1340 1285 1245
-36
1 Fan Only 850 800 750 665 600
2 Matched with 2.5 ton condensing unit 1080 950 910 850 775
3 Nominal 3 ton match without electric heat 1270 1230 1170 1120 1060
4 Nominal 3 ton match with electric heat 1440 1400 1330 1280 1240
5 High static application 1540 1475 1430 1380 1300
-42
1 Fan Only 990 915 860 810 725
2 Matched with 3 ton condensing unit 1190 1150 1100 1060 1020
3 Nominal 3.5 ton match without electric heat 1390 1350 1315 1280 1230
4 Nominal 3.5 ton match with electric heat 1665 1625 1585 1550 1510
5 High static application 1750 1710 1675 1640 1600
-48
1 Fan Only 1255 1210 1155 1115 1050
2 Matched with 3.5 ton condensing unit 1485 1450 1410 1365 1330
3 Nominal 4 ton match without electric heat 1720 1675 1630 1595 1550
4 Nominal 4 ton match with electric heat 1720 1675 1630 1595 1550
5 High static application 1840 1795 1755 1720 1680
-60
1 Fan Only 1100 1050 1000 925 830
2 Matched with 4 ton condensing unit 1625 1595 1565 1520 1490
3 Nominal 5 ton match without electric heat 1815 1780 1760 1730 1685
4 Nominal 5 ton match with electric heat 1900 1870 1835 1810 1765
5 High static application 1980 1955 1920 1890 1860
Table 2. BE5E Constant Torque Air Handler Wet Air Flow Data