BE5E Installation Instructions

507788-01BIssue 1818Page 12 of 20
Electrical wiring, disconnect means and over-
current protection are to be supplied by the
installer. Refer to the air handler rating plate
for maximum over-current protection, minimum
circuit ampacity, as well as operating voltage.
Select the proper supply circuit conductors in
accordance with tables 310-16 and 310-17 in the
National Electric Code, ANSI/NFPA No. 70 or tables 1
through 4 in the Canadian Electric Code, Part I, CSA
Standard C22.1.
The power supply must be sized and protected
according to the specications supplied on the product.
This air handler is factory-congured for 240 volt,
single phase, 60 cycles. For 208-volt applications, see
“208 Volt Conversion” later in this section.
Separate openings have been provided for 24V low
voltage and line voltage. Refer to the dimension
illustration of specic location.
This unit is provided with holes for conduit. Use
provided caps to seal holes not used.
Typical unit wiring (as well as wiring of optional eld-
installed electric heat) is given in Figure 14. Refer to
the instructions provided with the electric heat section
for proper installation.
USE COPPER CONDUCTORS ONLY
WARNING
1. Disconnect all power supplies.
2. Remove the air handler access panel.
3. Route the eld supply wires to the air handler electrical
connection box.
4. Use UL-listed wire nuts to connect the eld supply
conductors to the unit black and yellow leads, and the
ground wire to ground terminal marked GND.
5. Replace the air handler access panel.
SIDE
TOP
Figure 11. Electrical Connections
(Upow Conguration)
NOTE: To avoid the possibility of moisture damage to the
control in some right-hand discharge congurations, the
control panel can be relocated to the end panel as shown
in Figure 12.
TOP
SIDE
Figure 12. Control Panel Relocated to End Panel
(Left-Hand Horizontal Conguration)
208 Volt Conversion
1. Disconnect all power supplies.
2. Remove the air handler access panel.
3. Using the wiring diagram located on the unit access
panel as a reference, move the 2 connected black
transformer leads from the 240 volt terminal on the
transformer to the 208 volt terminal on the transformer.
208 / 240 VOLT TRANSFORMER
PRIMARY SECONDARY
240 Volts
208 Volts
Figure 13. Converting Unit from 240VAC to 208VAC