BE5V Specifications Sheet

COMPACT AIR HANDLER
BE5V
Page 9
BCE5V36 PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
ADJUST”
Jumper Setting
Jumper Speed Positions
“HEAT” Speed (W) First Stage “COOL” Speed (Y1)
Second Stage “COOL” Speed (Y1
+ Y2)
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 930 1155 1390 1530 640 815 970 1150 930 1155 1390 1530
NORM 830 1050 1260 1450 590 725 875 1025 830 1050 1260 1450
740 940 1135 1330 545 650 780 910 740 940 1135 1330
NOTES - The eect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL speed setting.
Lennox Harmony III™ Zoning System applications - minimum blower speed is 250 cfm.
BCE5V36 BLOWER MOTOR WATTS
AT “+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 111 132 152 193 226 246 271 282
Tap 2 188 215 242 271 295 327 391 412
Tap 3 298 325 361 395 433 474 491 515
Tap 4 464 503 516 537 526 527 529 522
First Stage “COOL” Speed
Tap 1 53 78 98 112 135 151 173 192
Tap 2 78 101 118 149 173 191 217 237
Tap 3 115 136 162 185 237 265 284 308
Tap 4 166 196 228 252 284 303 364 399
Second Stage “COOL
Speed
Tap 1 111 132 152 193 226 246 271 282
Tap 2 188 215 242 271 295 327 391 412
Tap 3 298 325 361 395 433 474 491 515
Tap 4 464 503 516 537 526 527 529 522
AT “NORM” SETTING (“Adjust” Jumper at NORM Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 79 102 128 170 189 210 225 254
Tap 2 138 165 191 219 243 300 328 347
Tap 3 225 249 287 315 351 377 407 429
Tap 4 342 384 425 456 510 531 533 525
First Stage “COOL” Speed
Tap 1 41 69 80 100 115 141 159 176
Tap 2 64 80 114 136 155 169 197 214
Tap 3 241 219 202 155 145 116 94 85
Tap 4 319 296 258 211 189 163 138 123
Second Stage “COOL
Speed
Tap 1 79 102 128 170 189 210 225 254
Tap 2 138 165 191 219 243 300 328 347
Tap 3 225 249 287 315 351 377 407 429
Tap 4 342 384 425 456 510 531 533 525