BE5V Specifications Sheet
COMPACT AIR HANDLER
BE5V
Page 7
AT “NORM” SETTING (“Adjust” Jumper at NORM Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 33 45 57 68 78 89 101 115
Tap 2 64 81 96 113 132 145 159 179
Tap 3 133 152 172 190 211 231 252 270
Tap 4 253 278 307 325 348 374 397 415
First Stage “COOL” Speed
Tap 1 26 36 39 52 62 73 93 102
Tap 2 37 45 57 66 76 90 100 113
Tap 3 62 80 94 108 123 135 152 171
Tap 4 88 108 128 145 162 181 195 214
Second Stage “COOL”
Speed
Tap 1 33 45 57 68 78 89 101 115
Tap 2 64 81 96 113 132 145 159 179
Tap 3 133 152 172 190 211 231 252 270
Tap 4 253 278 307 325 348 374 397 415
AT “–” (Minus) SETTING (“Adjust” Jumper at “–” Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 30 43 54 62 73 84 97 109
Tap 2 52 71 87 99 117 128 145 157
Tap 3 100 118 138 161 179 193 204 228
Tap 4 167 185 206 230 256 280 295 316
First Stage “COOL” Speed
Tap 1 23 29 42 48 60 75 88 93
Tap 2 31 39 54 62 76 86 96 105
Tap 3 46 56 70 84 93 107 115 133
Tap 4 72 87 105 121 141 158 175 188
Second Stage “COOL”
Speed
Tap 1 30 43 54 62 73 84 97 109
Tap 2 52 71 87 99 117 128 145 157
Tap 3 100 118 138 161 179 193 204 228
Tap 4 167 185 206 230 256 280 295 316
BCE5V30 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper Setting
Jumper Speed Positions
“HEAT” Speed (W) First Stage “COOL” Speed (Y1)
Second Stage “COOL” Speed (Y1
+ Y2)
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 680 885 1115 1340 490 635 770 930 680 885 1115 1340
NORM 620 810 1020 1220 440 575 715 845 620 810 1020 1220
– 550 725 905 1100 411 530 645 755 550 725 905 1100
NOTES - The eect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL speed setting. Lennox Harmony III™ Zoning System applica-
tions - minimum blower speed is 250 cfm.