BE5V Specifications Sheet

COMPACT AIR HANDLER
BE5V
Page 6
AT “–” (Minus) SETTING (“Adjust” Jumper at “–” Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 33 43 56 65 77 88 96 112
Tap 2 65 80 93 113 126 140 151 164
Tap 3 119 140 153 169 185 206 220 236
Tap 4 195 219 237 261 281 296 320 338
First Stage “COOL” Speed
Tap 1 23 35 43 52 63 73 85 96
Tap 2 37 45 54 70 76 86 99 110
Tap 3 59 73 86 102 113 128 140 152
Tap 4 88 102 119 137 154 165 185 201
Second Stage “COOL
Speed
Tap 1 33 43 56 65 77 88 96 112
Tap 2 65 80 93 113 126 140 151 164
Tap 3 119 140 153 169 185 206 220 236
Tap 4 195 219 237 261 281 296 320 338
BCE5V24 BLOWER MOTOR WATTS
AT “+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 40 50 60 74 86 95 112 124
Tap 2 82 100 116 136 151 163 185 197
Tap 3 173 190 213 236 257 283 300 316
Tap 4 290 318 339 363 379 407 447 463
First Stage “COOL” Speed
Tap 1 27 37 46 57 68 76 88 104
Tap 2 41 54 62 75 87 97 108 121
Tap 3 75 94 109 127 145 161 173 191
Tap 4 113 133 146 168 189 205 222 244
Second Stage “COOL
Speed
Tap 1 40 50 60 74 86 95 112 124
Tap 2 82 100 116 136 151 163 185 197
Tap 3 173 190 213 236 257 283 300 316
Tap 4 290 318 339 363 379 407 447 463
BCE5V24 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
ADJUST”
Jumper Setting
Jumper Speed Positions
“HEAT” Speed (W) First Stage “COOL” Speed (Y1)
Second Stage “COOL” Speed (Y1
+ Y2)
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 450 670 900 1120 340 450 650 770 450 670 900 1120
NORM 420 620 820 1050 300 400 600 700 420 620 820 1050
390 570 750 915 280 390 500 650 390 570 750 915
NOTES - The eect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL speed setting. Lennox Harmony III™ Zoning System
applications - minimum blower speed is 250 cfm.