BE5V Specifications Sheet

COMPACT AIR HANDLER
BE5V
Page 13
BE5V60 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
ADJUST”
Jumper Setting
Jumper Speed Positions
“HEAT” Speed (W) First Stage “COOL” Speed (Y1)
Second Stage “COOL” Speed (Y1
+ Y2)
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 1600 1835 2030 2190 1110 1285 1380 1615 1600 1835 2030 2190
NORM 1465 1675 1855 2085 1000 1160 1250 1470 1465 1675 1855 2085
1320 1500 1675 1890 895 1035 1115 1320 1320 1500 1675 1890
NOTES - The eect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL speed setting. Lennox Harmony III™ Zoning System applica-
tions - minimum blower speed is 450 cfm.
BE5V60 BLOWER MOTOR WATTS
AT “+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 330 360 403 444 488 521 563 600
Tap 2 469 505 564 616 649 685 735 776
Tap 3 631 671 734 782 832 894 931 974
Tap 4 903 957 1016 1015 1013 1002 1002 998
First Stage “COOL” Speed
Tap 1 146 166 194 223 267 300 340 379
Tap 2 195 221 252 278 319 358 383 427
Tap 3 225 260 286 319 357 399 427 466
Tap 4 339 382 417 447 494 532 567 611
Second Stage “COOL
Speed
Tap 1 330 360 403 444 488 521 563 600
Tap 2 469 505 564 616 649 685 735 776
Tap 3 631 671 734 782 832 894 931 974
Tap 4 903 957 1016 1015 1013 1002 1002 998
AT “NORM” SETTING (“Adjust” Jumper at NORM Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 251 288 320 355 391 440 463 514
Tap 2 348 397 433 482 515 565 607 650
Tap 3 472 524 578 614 664 704 749 810
Tap 4 696 740 792 856 886 939 984 983
First Stage “COOL” Speed
Tap 1 110 105 164 196 233 263 297 320
Tap 2 152 182 205 244 271 300 347 387
Tap 3 177 205 238 271 311 341 375 424
Tap 4 254 298 331 367 408 444 473 527
Second Stage “COOL
Speed
Tap 1 251 288 320 355 391 440 463 514
Tap 2 348 397 433 482 515 565 607 650
Tap 3 472 524 578 614 664 704 749 810
Tap 4 696 740 792 856 886 939 984 983