BE5V Specifications Sheet
COMPACT AIR HANDLER
BE5V
Page 5
BLOWER
BCE5V18 BLOWER MOTOR WATTS
AT “+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 46 61 74 86 99 111 124 138
Tap 2 97 115 132 145 162 178 196 213
Tap 3 185 205 229 245 268 282 300 316
Tap 4 340 366 392 417 439 459 488 488
First Stage “COOL” Speed
Tap 1 30 41 51 59 69 81 92 106
Tap 2 50 66 80 90 105 118 126 142
Tap 3 87 106 116 135 148 167 178 192
Tap 4 141 161 181 201 215 228 247 262
Second Stage “COOL”
Speed
Tap 1 46 61 74 86 99 111 124 138
Tap 2 97 115 132 145 162 178 196 213
Tap 3 185 205 229 245 268 282 300 316
Tap 4 340 366 392 417 439 459 488 488
AT “NORM” SETTING (“Adjust” Jumper at NORM Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 40 55 66 80 93 101 115 128
Tap 2 82 100 113 125 144 157 176 183
Tap 3 146 170 191 207 224 238 259 276
Tap 4 259 290 314 330 352 369 391 415
First Stage “COOL” Speed
Tap 1 28 37 46 58 67 79 89 102
Tap 2 45 59 70 85 96 107 119 133
Tap 3 74 88 102 120 132 145 161 171
Tap 4 115 131 147 162 185 195 210 229
Second Stage “COOL”
Speed
Tap 1 40 55 66 80 93 101 115 128
Tap 2 82 100 113 125 144 157 176 183
Tap 3 146 170 191 207 224 238 259 276
Tap 4 259 290 314 330 352 369 391 415
BCE5V18 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper Setting
Jumper Speed Positions
“HEAT” Speed (W) First Stage “COOL” Speed (Y1)
Second Stage “COOL” Speed
(Y1 + Y2)
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 500 705 925 1150 365 520 665 810 500 705 925 1150
NORM 465 650 850 1050 350 485 610 740 465 650 850 1050
– 420 600 760 950 320 425 560 680 420 600 760 950
NOTES - The eect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL speed setting. Lennox Harmony III™
Zoning System applications - minimum blower speed is 250 cfm.