BE5V Installation Instructions

507789-01B Issue 1818 Page 17 of 24
BE5V30 Blower Performance
0 through 0.80 in. w.g. External Static Pressure Range
ADJUST
Jumper Setting
Jumper Speed Positions
“HEAT” Speed First Stage “COOL” Speed Second Stage “COOL” Speed
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 680 885 1115 1340 490 635 770 930 680 885 1115 1340
NORM 620 810 1020 1220 440 575 715 845 620 810 1020 1220
550 725 905 1100 411 530 645 755 550 725 905 1100
NOTES - The effect of static pressure, lter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL
speed setting.
Zoning System applications - minimum blower speed is 250 cfm.
BE5V36 Blower Performance
0 through 0.80 in. w.g. External Static Pressure Range
ADJUST
Jumper Setting
Jumper Speed Positions
“HEAT” Speed First Stage “COOL” Speed Second Stage “COOL” Speed
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 930 1155 1390 1530 640 815 970 1150 930 1155 1390 1530
NORM 830 1050 1260 1450 590 725 875 1025 830 1050 1260 1450
740 940 1135 1330 545 650 780 910 740 940 1135 1330
NOTES - The effect of static pressure, lter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL
speed setting.
Zoning System applications - minimum blower speed is 250 cfm.
BE5V42 Blower Performance
0 through 0.80 in. w.g. External Static Pressure Range
ADJUST
Jumper Setting
Jumper Speed Positions
“HEAT” Speed First Stage “COOL” Speed Second Stage “COOL” Speed
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 1130 945 1575 1810 780 945 1110 1275 1130 945 1575 1810
NORM 1020 1255 1440 1650 710 860 1000 1160 1020 1255 1440 1650
920 1135 1300 1490 670 780 910 1040 920 1135 1300 1490
NOTES - The effect of static pressure, lter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL
speed setting.
Zoning System applications - minimum blower speed is 450 cfm.
BE5V48 Blower Performance
0 through 0.80 in. w.g. External Static Pressure Range
ADJUST
Jumper Setting
Jumper Speed Positions
“HEAT” Speed First Stage “COOL” Speed Second Stage “COOL” Speed
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 1375 1600 1820 2185 960 1125 1285 1620 1375 1600 1820 2185
NORM 1260 1455 1655 2085 885 1035 1185 1475 1260 1455 1655 2085
1125 1310 1490 1885 790 925 1060 1330 1125 1310 1490 1885
NOTES - The effect of static pressure, lter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL
speed setting.
Zoning System applications - minimum blower speed is 450 cfm.