BE5V Specifications Sheet
COMPACT AIR HANDLER
BE5V
Page 11
AT “NORM” SETTING (“Adjust” Jumper at NORM Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 116 146 168 196 221 250 286 305
Tap 2 188 215 243 266 295 319 348 383
Tap 3 270 300 327 353 384 417 450 474
Tap 4 375 416 459 500 517 556 588 618
First Stage “COOL” Speed
Tap 1 57 78 107 134 151 171 192 225
Tap 2 85 111 135 158 197 213 226 246
Tap 3 118 138 163 186 219 254 291 305
Tap 4 170 198 217 247 267 295 328 380
Second Stage “COOL”
Speed
Tap 1 116 146 168 196 221 250 286 305
Tap 2 188 215 243 266 295 319 348 383
Tap 3 270 300 327 353 384 417 450 474
Tap 4 375 416 459 500 517 556 588 618
AT “–” (Minus) SETTING (“Adjust” Jumper at “–” Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 96 119 138 162 191 227 247 266
Tap 2 153 171 200 226 249 286 303 348
Tap 3 204 237 259 286 319 336 371 401
Tap 4 282 312 353 384 417 441 468 503
First Stage “COOL” Speed
Tap 1 56 74 98 121 131 169 178 200
Tap 2 79 93 115 140 165 188 199 218
Tap 3 98 117 138 170 196 228 250 260
Tap 4 126 148 175 194 222 254 300 322
Second Stage “COOL”
Speed
Tap 1 96 119 138 162 191 227 247 266
Tap 2 153 171 200 226 249 286 303 348
Tap 3 204 237 259 286 319 336 371 401
Tap 4 282 312 353 384 417 441 468 503
BE5V48 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
“ADJUST”
Jumper Setting
Jumper Speed Positions
“HEAT” Speed (W) First Stage “COOL” Speed (Y1)
Second Stage “COOL” Speed (Y1
+ Y2)
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 1375 1600 1820 2185 960 1125 1285 1620 1375 1600 1820 2185
NORM 1260 1455 1655 2085 885 1035 1185 1475 1260 1455 1655 2085
– 1125 1310 1490 1885 790 925 1060 1330 1125 1310 1490 1885
NOTES - The eect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL speed setting. Lennox Harmony III™ Zoning System
applications - minimum blower speed is 450 cfm.