BE5V Specifications Sheet

COMPACT AIR HANDLER
BE5V
Page 4
ELECTRICAL
1. For 208 volt use .751 correction factor for kW and Btuh
2. 12.5kW, 15 and 20kW (2 stage models) require 2 supply circuits
3. Circuit #1 includes blower motor amps except 20kW models
Model
Heating Capacity (240V)
Blower
Amps
Min. Circuit Ampacity
Max. Circuit Breaker
Size
Single Point Power Supply
Nominal
Heater
Size kW
kW Btuh
208V 240V 208V 240V 208V 240V
1 2 1 2 1 2 1 2 Amps Fuse Amps Fuse
BE5V18
0 0 0
3.9
4.9 4.9 15 15
5 4.8 16400 27 30 30 30
7.5 7.5 25600 39 44 40 45
10 9.6 32700 48 55 50 60
BE5V24
0 0 0
3.9
4.9 4.9 15 15
5 4.8 16400 27 30 30 30
7.5 7.5 25600 39 44 40 45
10 9.6 32700 48 55 50 60
BE5V30
0 0 0
3.9
4.9 4.9 15 15
5 4.8 16400 27 30 30 30
7.5 7.5 25600 39 44 40 45
10 9.6 32700 48 55 50 60
12.5 12.5 42600 42 19 48 22 45 20 50 25 61 70 70 70
15 14.4 49100 48 22 55 25 50 25 60 25 70 70 80 80
BE5V36
0 0 0
3.9
6.5 4.9 15 15
5 4.8 16400 27 30 30 30
7.5 7.5 25600 39 44 40 45
10 9.6 32700 48 55 50 60
12.5 12.5 42600 42 19 48 22 45 20 50 25 61 70 72 80
15 14.4 49100 50 22 57 25 50 25 60 25 72 80 82 90
BE5V42
0 0 0
6.9
8.6 6.5 15 15
5 4.8 16400 30 34 30 35
7.5 7.5 25600 42 48 45 50
10 9.6 32700 52 59 60 60
12.5 12.5 42600 46 19 52 22 50 20 60 25 65 70 74 80
15 14.4 49100 52 22 59 25 60 25 60 25 74 80 84 90
BE5V48
0 0 0
6.9
8.6 8.6 15 15
5 4.8 16400 30 34 30 35
7.5 7.5 25600 42 48 45 50
10 9.6 32700 52 59 60 60
12.5 12.5 42600 46 19 52 22 50 20 60 25 65 70 74 80
15 14.4 49100 53 22 60 25 60 25 60 25 75 80 85 90
20 19.2 65500 53 43 60 50 60 45 60 50 96 100 110 110
BE5V60
0 0 0
6.9
9.5 8.6 15 15
5 4.8 16400 30 34 30 35
7.5 7.5 25600 42 48 45 50
10 9.6 32700 52 59 60 60
12.5 12.5 42600 46 19 52 22 50 20 60 25 65 70 74 80
15 14.4 49100 53 22 60 25 60 25 60 25 75 80 85 90
20 19.2 65500 53 43 60 50 60 45 60 50 96 100 110 110