BE5V Specifications Sheet

COMPACT AIR HANDLER
BE5V
Page 5
BLOWER
BCE5V18 BLOWER MOTOR WATTS
AT “+” (Plus) SETTING (“Adjust” Jumper at “+” Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 46 61 74 86 99 111 124 138
Tap 2 97 115 132 145 162 178 196 213
Tap 3 185 205 229 245 268 282 300 316
Tap 4 340 366 392 417 439 459 488 488
First Stage “COOL” Speed
Tap 1 30 41 51 59 69 81 92 106
Tap 2 50 66 80 90 105 118 126 142
Tap 3 87 106 116 135 148 167 178 192
Tap 4 141 161 181 201 215 228 247 262
Second Stage “COOL
Speed
Tap 1 46 61 74 86 99 111 124 138
Tap 2 97 115 132 145 162 178 196 213
Tap 3 185 205 229 245 268 282 300 316
Tap 4 340 366 392 417 439 459 488 488
AT “NORM” SETTING (“Adjust” Jumper at NORM Setting)
Jumper Speed Positions
Motor Watts @ Various External Static Pressures - in. wg.
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
“HEAT” Speed
Tap 1 40 55 66 80 93 101 115 128
Tap 2 82 100 113 125 144 157 176 183
Tap 3 146 170 191 207 224 238 259 276
Tap 4 259 290 314 330 352 369 391 415
First Stage “COOL” Speed
Tap 1 28 37 46 58 67 79 89 102
Tap 2 45 59 70 85 96 107 119 133
Tap 3 74 88 102 120 132 145 161 171
Tap 4 115 131 147 162 185 195 210 229
Second Stage “COOL
Speed
Tap 1 40 55 66 80 93 101 115 128
Tap 2 82 100 113 125 144 157 176 183
Tap 3 146 170 191 207 224 238 259 276
Tap 4 259 290 314 330 352 369 391 415
BCE5V18 BLOWER PERFORMANCE
0 through 0.80 in. w.g. External Static Pressure Range
ADJUST”
Jumper Setting
Jumper Speed Positions
“HEAT” Speed (W) First Stage “COOL” Speed (Y1)
Second Stage “COOL” Speed
(Y1 + Y2)
1 2 3 4 1 2 3 4 1 2 3 4
cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm cfm
+ 500 705 925 1150 365 520 665 810 500 705 925 1150
NORM 465 650 850 1050 350 485 610 740 465 650 850 1050
420 600 760 950 320 425 560 680 420 600 760 950
NOTES - The eect of static pressure, filter and electric heater resistance is included in the air volumes listed.
First stage cooling air volume is 70% of COOL speed setting. Continuous blower speed is approximately 50% of COOL speed setting. Lennox Harmony III™
Zoning System applications - minimum blower speed is 250 cfm.