BG961UHE Gas Furnace Installation Manual

507768-02B Page 51 of 56Issue 1904
BG961UH110CE20 Performance (Less Filter)
External
Static
Pressure
in. w.c.
Air Volume / Watts at Various Blower Speeds
Bottom Return Air, Side Return Air with Optional Return Air Base, Return Air from
Both Sides or Return Air from Bottom and One Side.
Single Side Return Air - Air volumes in bold require eld fabricated transition to
accommodate 20 x 25 x 1 in. air lter in order to maintain proper air velocity.
High Medium - High Medium Medium - Low Low High Medium - High Medium Medium - Low Low
cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts
0.00 2220 655 1975 440 1800 325 1665 390 1050 180 2180 685 1910 460 1750 345 1660 285 1430 195
0.10 2185 680 1925 460 1750 345 1625 285 1440 200 2155 705 1885 480 1720 360 1610 295 1415 205
0.20 2150 705 1880 480 1710 365 1590 300 1390 220 2130 725 1855 495 1685 380 1565 305 1380 220
0.30 2110 720 1850 495 1680 380 1560 320 1350 230 2085 745 1825 510 1655 390 1535 325 1335 230
0.40 2080 735 1810 520 1650 405 1515 330 1310 245 2060 760 1795 530 1625 405 1495 340 1295 245
0.50 2045 755 1785 530 1610 415 1470 350 1265 255 2030 775 1765 545 1585 425 1450 355 1255 265
0.60 2010 775 1740 545 1575 430 1440 370 1220 270 1995 785 1725 565 1550 435 1420 370 1205 275
0.70 1980 790 1705 565 1525 450 1400 375 1170 280 1960 795 1690 575 1505 455 1385 385 1165 290
0.80 1950 795 1670 580 1485 460 1360 390 1140 293 1895 790 1650 590 1465 470 1335 395 1120 295
NOTE: All air is measured external to unit without lter (lter not furnished - eld provided)