REFRIGERATION DATA
Outdoor Model
Charge
(oz)
6
Refrigerant Connection
Refrigerant Line Size Indoor Expansion Device
Outdoor Indoor (DTC)
7
Suction Liquid Suction Liquid Suction Liquid Piston TXV
1
4AC13*18P-10/11 65 5/8 3/8 3/4 3/8 5/8 or 3/4
3
3/8 or 1/4
2
0.053 H4TXV01
4AC13*24P-10/11 62 5/8 3/8 3/4 3/8 5/8 or 3/4
3
3/8 or 1/4
2
0.057 H4TXV01
4AC13*30P-10 82 3/4 3/8 3/4 3/8 3/4 3/8 0.063 H4TXV01
4AC13*30P-11 82 3/4 3/8 3/4 3/8 3/4 3/8 0.059 H4TXV01
4AC13*36P-10/11 84 3/4 3/8 7/ 8 3/8 3/4 3/8 0.072 H4TXV02
4AC13*42P-10/11 104 3/4 3/8 7/ 8 3/8 3/4
5
3/8 0.074 H4TXV02
4AC13*48P-10/11 124 7/ 8 3/8 7/ 8 3/8 7/ 8 3/8 0.082 H4TXV02
4AC13*60P-10/11 144 7/8 3/8 7/ 8 3/8 7/8 or 1-1/8
4
3/8 0.090 H4TXV02
Note:
1 Required to achieve AHRI rating. If NA (Not Applicable) is in the piston column, then TXV is required.
2 Use 3/8 if over 24 feet of line set
3 Use 3/4 if over 24 feet of line set
4 Use 1-1/8 if over 24 feet of line set. Adapter provided with OD unit
5 Use 7/8 if over 24 feet of line set
6 Charged for 15 ft of line set
7 DTC = Designated Tested Combination
COOLING PERFORMANCE WITH DTC
1
Outdoor Model Indoor Model Capacity (BTUH) EER SEER
4AC13*18P-10/11 E(C,M,U)1P24(A,B)+TDR 17600 11 13
4AC13*24P-10/11 E(C,M,U)1P24(A,B)+TDR 22800 11 13
4AC13*30P-10/11 E(C,M,U)1P24(A,B)+TDR 28000 10.7 13
4AC13*36P-10/11 E(C,H,M,U)1P36(B,C)+TDR 34000 10.5 13
4AC13*42P-10/11 E(C,H,M,U)1P43C+TDR 40000 10.7 13
4AC13*48P-10/11 E(C,H,U)1P49C+TDR 47000 11 13
4AC13*60P-10/11 E(C,H,U)1P49C+TDR 57000 10.7 13
1 DTC = Designated Tested Combination