Installation & Operation Instructions
WIRELESS LINKING (PAIRING)
Linking a sensor with a wireless load controller is quickly done via the following procedure:
Step 1. Enter pairing mode by holding down the wireless load controller button for 3 seconds until the LED starts alternating white then blue, then release.
Step 2. At the sensor, hold down the programming button for 3 seconds until the LED starts alternating white then blue. Releasing will link the sensor with any device in pairing mode
(see note 1 below). The lights will toggle once as conrmation.
Step 3. Repeat step 2 to link another sensor or device.
Step 4. When all devices have been linked, exit pairing mode on the wireless load controller by pressing the button 1 time. Pairing will also be automatically closed
after 15 minutes of no new devices being linked.
Note 1: When in pairing mode, the alternating LED colors on the wireless load controller will periodically pause and blink out the total number of linked devices. There will be no blinks
during the pause until the rst device is linked.
CONFIGURATION
SENSOR HEARTBEAT TIME
The period between transmissions of a wireless sensor is referred to as the sensor’s “heartbeat”. For best battery life performance, it is recommended that the default heartbeat time of
1 minute be used. However, if a linked load controller is using the 30 second time delay option, the sensor’s heartbeat needs to also be changed to 30 seconds. Note that doing so will
decrease battery life.
SETTING # DESCRIPTION
2 30 Seconds
3 1 Minute (Default)
CHANGING THE HEARTBEAT TIME
1Read through the above list and note the number of the desired setting (e.g. 2 = 30 secs.)
2 Press and release the unit’s pushbutton 3 times, then wait 2 seconds.The White LED will blink back the number of the current setting (repeats 3x before exiting).
3 Interrupt blink back by pressing the button the number times equal to the new desired setting (e.g. 2 = 30 secs).
4 The LED will blink back the new setting number as conrmation and will be saved after three conrmations. After the third conrmation sequence, a successful save will be indicated by
two sets of rapid White ashes. If the Blue LED rapid ashes twice, save was unsuccessful and process should be started over.
STEP 1
WALL SWITCH OR POWER PACK
STEP 2 & STEP 3
WIRELESS SENSOR
STEP 4
WALL SWITCH OR POWER PACK
SWX-401-B
HOLD
FOR 3 SEC
SWX-851
HOLD
FOR 3 SEC
SWX-950
HOLD
FOR 3 SEC
SWX-851
PRESS ONCE
SWX-950
PRESS ONCE
OR OR