Operating instructions

PROGRAMMING - DIAGNOSTIC TEST (continued)
The message "Test Done"
should be on the display.
P re s s t h e POWE R ke y t o re se t
the controller. The controller
should restart with the message
"BLOOMFIELD" and date.
Probe Test:
Two numbers will be displayed:
1. The left number determines whether the WATER-sensing
probe is in contact with water.
a. A number of "0" (or close to 0) means that water is in
contact with the probe.
b. A number of "255" (or close to 255) means water is not in
contact with the probe.
2. The right number represents what the TEMPERATURE-
sensing probe reads. The table below is an approximate
correlation between the value and the temperature the probe
is sensing:
a. A number less than "10" indicates that the probe is not
properly connected to the board
b. A number higher than "155" indicate a defective probe.)
Testing Complete!
18
Number
(Right Side)
Approximate
Water Temp.
10
Probe not
connected
20 74ºF
25 83ºF
30 92ºF
120 181ºF
125 186ºF
130 191ºF
135 196ºF
140 201ºF
150 206ºF
155
Defective
Probe
675 p/ n 74346 SS-2 Programming Manual