Operating instructions
PROGRAMMING - DIAGNOSTIC TEST (continued)
The message "Test Done"
should be on the display.
P re s s t h e POWE R ke y t o re se t
the controller. The controller
should restart with the message
"BLOOMFIELD" and date.
Probe Test:
Two numbers will be displayed:
1. The left number determines whether the WATER-sensing
probe is in contact with water.
a. A number of "0" (or close to 0) means that water is in
contact with the probe.
b. A number of "255" (or close to 255) means water is not in
contact with the probe.
2. The right number represents what the TEMPERATURE-
sensing probe reads. The table below is an approximate
correlation between the value and the temperature the probe
is sensing:
a. A number less than "10" indicates that the probe is not
properly connected to the board
b. A number higher than "155" indicate a defective probe.)
Testing Complete!
18
Number
(Right Side)
Approximate
Water Temp.
≤ 10
Probe not
connected
20 74ºF
25 83ºF
30 92ºF
↓ ↓
120 181ºF
125 186ºF
130 191ºF
135 196ºF
140 201ºF
150 206ºF
≥ 155
Defective
Probe
675 p/ n 74346 SS-2 Programming Manual