Repair manual

MT1828
1
OVEN S PECIFICATIONS
VENTILA TION REQUIREMENTS
The hood should completely cover the unit with an
overhang of at least 6” (15 cm) on all sides not adja-
cent to a wall. The distance from the floor to the
lower edge of the hood should not exceed 7’ (2.1
m). The ventilation system should replace 80% of
the exhaust volume with fresh make up air.
TABLE 1 should be used as a guideline.
Single Double Triple
CFM 400-500 900-1000 1200-1500
M
3
/min 14 - 17 28-34 42-51
TABLE 1
ELECTRICAL SPECIFICATIONS
NOTE: Three Phase hookup is not permitted on
gas models.
Installations within the U.S.
The MT1828G requires a 15 Amp, 60HZ, 1Φ,
208-240VAC, 4 wire service consisting of L1, L2,
neutral and ground. See FIGURE 1. Use 90_Cwire
and size t o National Electric or local codes.
The MT1828E is available in either 1Φ or 3Φ mod-
els. Single phase models require a 60Hz,
208/240VAC, 3 wire service consisting of L1, L2
and ground. Three phase models require a 60Hz,
208/240VAC, 4 wire service consisting of L1, L2, L3
and ground. See FIGURE 1. W iring from the power
source to any of these units must be a minimum of
#8AWGcopperstrandedwireorlargerfor3phase
and #4 AWG for 1 phase.
MT1828G
L1
N
L2
120
120
208-240
OvenSupply
MT1828E Single Phase MT1828E Three Phase Delta System
L1
208/240
OvenSupply
L2
L1
L2
L3
208/240
OvenSupply
FIGURE 1