Repair manual

TROUBLESHOOTING
5 --- 2
COMPUTER CONTROL SYSTEM
POSSIBLE CAUSE(S) SUGGESTED REMEDY
Symptom #1 --- Computer controller displays: PROBE - OPEN - PROBE - SHORT and
alarm buzzer sounds
D
Internal problem with computer controller.
D
Loose connections at computer controller.
D
Shorted or open RTD probe.
D
Verify display integ. in the 2nd level program-
ming. If t he controller has been programmed the
computer may need to be replaced.
D
Tighten connections.
D
Use the chart in the Technical Appendix (page
NO TAG) to determine if probe is bad. Replace if
necessary.
Symptom #2 --- Computer controller displays: ERROR - HIGH - TEMP - LIMIT
D
Actual temperature exceeds programmed limit
value. Default 605_F (319_C).
D
Internal problem with computer controller.
D
Faulty burner valve relay. Replace relay.
D
Faulty computer cables
D
Verify display integ. in the 2nd level program-
ming. If t he controller has been programmed the
computer may need to be replaced.
Symptom #3 --- Computer controller displays: MTR-SPD
D
Motor speed does not match set point.
D
Motor indicated that the computer is not receiv-
ing a signal from the pickup.
D
Recalibrate the motor speed. See Calibration
and Adjustment (page 3---8).
D
Fuses on the control board may have blown.
Check and replace if needed.
D
Wires from the pickup are not connected or bro-
ken. Connect or replace.