Repair manual

INSTALLATION
9 --- 4
PLUMBING CONNECTIONS
WATER CONNECTION
Connect the appliance to quality water via a pres-
sure hose with 3/4” (19mm) couplings. See
FIGURE 3 for connections. A shut off valve is to be
provided adjacent to the oven.
WARNING!!
Operating the appliance without the water
regulator i n s t a lled wi ll i n validate your war-
ranty.
Water must meet the following minimum require-
ments:
D
Total Dissolved Solids (TDS) content will not
exceed 30 parts per million.
D
WaterPHmustbe7.0orhigher
WARNING!!
The use of poor quality water will invali-
date your warranty.
BC14E
Cold Water
Water Connections
Rear of Appliance
FIGURE 3
STEAM CONNECTION FOR BC14EDS
Steam supply line is 3/4” NPT. Steam must be clean,
dry and potable. A particle screen and bucket trap
may be needed and are recommended. 60 lbs per
hour is the maximum usage per oven. Steam supply
pressure should not exceed 40 to 50 psi. The flo w
pressure is 1-1/2 to 3-1 /2 psi and is set at the steam
pressure regulator supplied inside the oven.
DRAIN CONNECTION
The steam vent assemblies are constructed of 2”
DWV copper piping reduced to 1-1/2 D WV pipe. If
the vent system is not purchased as an option
(R9381), Blodgett Combi recommends plumbing
the oven as shown in FIGURE 4.
Thesteamventshouldberuntoanopenfloor
drain avoiding flexible hose that could sag and al-
low trapped water to accumulate. The customer
must supply the piping from the oven to the drain.
Connect the drip pan drain to the steam vent w ith
1.125 I. D. hose.
Use the drain vent assembly and a 2” (50.8mm)
pipe for drain connection.
Customer supplied
2” (50.8mm) drain
waste vent piping
Coupling
FIGURE 4
Specific water/drain connection for City of Los
Angeles
1. Each drain line from the appliance shall be
routedwithoutdipsorsagstoterminateabove
the flood level rim of an approved indirect
waste receptor.
2. The a ppliance shall be installed in accordance
with the manufacturer’ s printed instructions
and the LAPC and LAMC, 1999 editions.
3. A backflow protection device shall be installed
on the potable w ater system directly ahead of
the appliance. The backflow protection device
shall be any of the following: an approved pres-
sure type vacuum breaker installed at least 12”
above the highest point of use, a double check
valve back flow preventer or a reduced pres-
sure principal backflow preventer.