Instruction Manual
Charge on.
Page 9 o f 3 7 Blink IQ 2 0 0
Level 2 AC EVSE Instruction Manual 1 0 / 9 / 2 0 1 9
5 .2 . Conduit & Brea k er Size Guide
All Specifications are Per Charging Station or Port
Max. Output
(Charging)
Current
Typical Circuit
Breaker (CB)
3
Typical W ire Specs
3
Typical
Conduit
Size
3
Blink IQ 200
Enclosure Input
Conduit Size
N otes / Assumptions
12A
See Note Below
15A
Two #12AW G W ires (Line)
One #12AW G W ire (Ground)
1/ 2"
-W ay Distance
16A
See Note Below
20A
Two #10AW G W ires (Line)
One #12AW G W ire (Ground)
3/ 4"
-W ay Distance
24A
See Note Below
30A
Two #8AW G W ires (Line)
One #10AW G W ire (Ground)
3/ 4"
-W ay Distance
32A
See Note Below
40A
Two #8AW G W ires (Line)
One #10AW G W ire (Ground)
3/ 4"
-W ay Distance
40A
See Note Below
50A
Two #6AW G W ires (Line)
One #8AW G W ire (Ground)
3/ 4"
-W ay Distance
64A
See Note Below
80A
Two #4AW G W ires (Line)
One #8AW G W ire (Ground)
One-W ay Distance
72A
See Note Below
90A
Two #3AW G W ires (Line)
One #8AW G W ire (Ground)
-W ay Distance
80A
Default Setting
100A
Two #2AW G W ires (Line)
One #8AW G W ire (Ground)
-W ay Distance
3
Consult with a licensed contractor, licensed electrician, or trained installation expert to ensure compliance with local building codes and safety standards.
Table 1
Co nduit and Breaker Size G uide
CAUTION W ARN IN G: RISK O F FIRE
All charg ing pro ducts are preco nfigured to allo w a Max. O utput (Charg ing) Current o f 8 0 A. To o perate the
pro duct at a reduced current, the M a x Ampera ge FW Setting MUST
(See Instructions in Section 7 .2 Cha nging the M a x imum Output (Cha rging) Current of a Cha rging
Sta tion).
CAUTION W ARN IN G: RISK O F FIRE
To reduce the risk o f the fire, co nnect o nly to a circuit pro vided with (CB - Table 1 ) amperes maximum branch
circuit o vercurrent pro tection in acco rdance with the N atio nal Electrical Co de, AN SI/ NFPA 7 0 , and the Canadian
Electrical Co de, Part I, C2 2 .2 .